Line Sentinel™The INCON TS-LLD Line Leak Detector uses patented, flow-based technology to perform multiple line tightness tests. |
The INCON TS-LLD line leak detector performs a variety of tests for environmental compliance.
The presence of the integral in-line check valve of the TS-LLD during normal operation creates a pressure drop which will reduce the total flow potential of the submersible pump. Some of the pressure drop can be compensated for by upgrading the submersible pump motor. To ensure desirable flow rates are achieved we do not recommend TS-LLD in the following sites:
In such cases we recommend our AutoLearn™ pressure based electronic leak line detector.
The TS-LLD can be used in most pressurized applications, in any new or existing turbine pump housing and can be used in place of a mechanical leak detector.
| PART NUMBER | DESCRIPTION |
|---|---|
| TS-CU | Control Unit |
| TS-LSU | Leak Sensor Unit |
| TS-FPU | Face Plate Unit |
| TS-FC | Line Filter Capacitor |
| 020-1503 | Hardware Kit |
| 430-0010 | 1/2 AMP Fuse |
| 010-0072 | Control Unit Terminal Interface Board |
| Dimensions in inches/millimeters CU LSU (H x D) |
4.35" x 3.35" x 2.31"/85.1 mm x 110.5 mm x 58.7 mm 23.5" x 2.4"/596.9 mm x 61 mm |
| Gross leak test (3.0 gph) | Yes |
| Monthly test (0.2 gph) | Yes |
| Annual test (0.1 gph) | Yes |
| Indicates number of days since 0.2 gph test passed |
Yes |
| LED unit | Yes |
| Positive shut down | Yes |
| Tank Sentinel(R) interface | Yes |
| Fuel compatibility | Gasoline and diesel motor fuels |
| PART NUMBER | DESCRIPTION |
|---|---|
| 115 VAC, 50/60 Hz Versions | |
| TS-LLD/FE | Electronic Line Leak Detector with a FE Petro Installation Adaptor (one required for each submersible pump) |
| TS-LLD/RJ | Electronic Line Leak Detector with a Red Jacket Installation Adaptor (one required for each submersible pump) |
| TS-LLD/RJQ | Electronic Line Leak Detector with a Red Jacket Quatum Installation Adaptor (one required for each submersible pump) |
Note: