Fueling Products

Fuel Management Systems

Other Solutions

Slideshow image

Line Sentinel™

The INCON TS-LLD Line Leak Detector uses patented, flow-based technology to perform multiple line tightness tests.

Features/Capabilities

Features

  • The TS-LLD leak detector performs gross leak tests after each dispense (3 gph), the monthly 0.2 gph test and the annual 0.1 gph test.
  • Performs positive shut down if a leak is detected.
  • Tests performed at full pump pressure to ensure integrity of lines.
  • Carries numerous regulatory approvals.
  • Low-cost, wireless installation retrofits easily into the existing submersible turbine pump housings without excavation.

Capabilities

The INCON TS-LLD line leak detector performs a variety of tests for environmental compliance.

  • Eliminates slow-flow problems associated with mechanical leak detectors.
  • Immediately identifies leaks even in changing thermal conditions, unlike mechanical LLDs.
  • Performs continuous testing using highly sensitive volumetric flow technology.
  • Continuously performs self-diagnostic test to ensure proper system operation.

Note

The presence of the integral in-line check valve of the TS-LLD during normal operation creates a pressure drop which will reduce the total flow potential of the submersible pump. Some of the pressure drop can be compensated for by upgrading the submersible pump motor. To ensure desirable flow rates are achieved we do not recommend TS-LLD in the following sites:

  • Where it is imperative to achieve 10 gpm.
  • Sites that frequently have more than 4 nozzles open at a time.

  • In such cases we recommend our AutoLearn™ pressure based electronic leak line detector.

Applications

The TS-LLD can be used in most pressurized applications, in any new or existing turbine pump housing and can be used in place of a mechanical leak detector.

  • Third party certified with 100% probability of leak detection and a 0% probability of false alarm.
  • Supports rigid, fiberglass and flexible piping systems.
  • Line leak test failure indicated by alarm. Works as a stand alone unit or it can be interfaced with INCON Tank Sentinel® Automatic Tank Gauge systems.

Spare Parts


PART NUMBER DESCRIPTION
TS-CU Control Unit
TS-LSU Leak Sensor Unit
TS-FPU Face Plate Unit
TS-FC Line Filter Capacitor
020-1503 Hardware Kit
430-0010 1/2 AMP Fuse
010-0072 Control Unit Terminal Interface Board

Specifications

 
Dimensions in inches/millimeters
CU
LSU (H x D)
4.35" x 3.35" x 2.31"/85.1 mm x 110.5 mm x 58.7 mm
23.5" x 2.4"/596.9 mm x 61 mm
Gross leak test (3.0 gph) Yes
Monthly test (0.2 gph) Yes
Annual test (0.1 gph) Yes
Indicates number of days since
0.2 gph test passed
Yes
LED unit Yes
Positive shut down Yes
Tank Sentinel(R) interface Yes
Fuel compatibility Gasoline and diesel motor fuels

Ordering Information


PART NUMBERDESCRIPTION
115 VAC, 50/60 Hz Versions
TS-LLD/FE Electronic Line Leak Detector with a FE Petro Installation Adaptor (one required for each submersible pump)
TS-LLD/RJ Electronic Line Leak Detector with a Red Jacket Installation Adaptor  (one required for each submersible pump)
TS-LLD/RJQ Electronic Line Leak Detector with a Red Jacket Quatum Installation Adaptor (one required for each submersible pump)

Note:

  • FE is a trademark of FE PETRO.
  • RJ = Red Jacket, trademark of the Veeder Root Co.